Fire extinguisher inspection

Every portable extinguisher in a workplace needs two kinds of attention: a quick monthly look by you or your staff, and a yearly maintenance visit by a trained technician who services the unit and hangs a dated tag on it.

On top of the yearly visit, some extinguishers have longer cycles: a six-year teardown for stored-pressure dry chemical units, and hydrostatic tests every five or twelve years depending on the type. The tag on each unit is the record an inspector looks at first.

Rules last checked Oct 23, 2026. Sources are at the foot of the page.

What the code asks for

Applies when
Portable fire extinguishers on site (required by the fire code or OSHA for a workplace).
What the pro does
The technician checks, weighs or tests each unit, replaces worn parts, recharges where needed, and attaches a dated service tag.
Who may do it
OSHA makes the employer responsible but sets no licence. NFPA 10 expects trained, qualified service people. Many states license the company and technician (see Texas and Florida entries).
Also on its own cycle
  • Six-year emptying and full maintenance (stored-pressure dry chemical): every 6 years. Applies to stored-pressure dry chemical units that need a 12-year hydrostatic test. Disposable non-refillable units are exempt.
  • Hydrostatic test every 5 years (CO2, water, stainless steel dry chemical and similar): every 5 years.
  • Hydrostatic test every 12 years (stored-pressure dry chemical in mild steel, aluminum or brass shells, halon): every 12 years.
Your own checks
Visual check every month: unit in place, gauge in the green, pin and tamper seal intact, no damage. Initial a tag or log each time.
Kept on site as your record
The service company tags each unit and keeps its report. The employer keeps the annual maintenance record for one year after the last entry or the life of the shell, whichever is less. Some cities also want reports submitted to the fire marshal.
Source: National code baseline

NFPA sells its codes rather than publishing them, so these are fire and health authorities quoting the code. They are national code, not rules for that city or state.

What it costs to miss

  • In Texas, a unit with a problem gets a red tag, and the technician has to tell the local fire marshal within 24 hours.
  • OSHA makes the employer, not the service company, responsible for the annual maintenance record.

Where the local rule differs

The state and city rules we have on file for fire extinguisher inspection, and how the paperwork gets filed in each.

WhereHow oftenWho may do itFiling
FloridaEvery yearA fire equipment dealer licensed by the Division of State Fire Marshal (Class A, B or C for extinguishers) and a technician with a valid permit.It is unlawful to service a unit without attaching a completed tag. Each six-year maintenance is recorded on a decal on the shell naming the agency.
TexasEvery yearA Type B (portable extinguisher), Type A or Type PL licensee working for a company with a Texas State Fire Marshal's Office Extinguisher Certificate of Registration. DOT cylinder hydrostatic tests need a Type C registered company.The licensee attaches a signed service tag after any service. For a red tag the licensee must tell the owner in writing, and tell the local fire marshal within 24 hours and send a copy of the owner notice within three business days.

When is yours due?

Pick your state, add the month from your tag, and see the next date and the rule behind it. Then book a licensed pro if you want one.

Optional. Used to find pros nearby.

What's on site?
  • The month punched on the tag is enough.

Free. No account needed.

Questions about fire extinguisher inspection

How often do fire extinguishers need to be inspected?

A visual check every month by you or your staff, and maintenance by a trained technician once a year. Stored-pressure dry chemical units also get a six-year internal maintenance, and shells are hydrostatically tested every five or twelve years depending on the type.

Who is allowed to inspect fire extinguishers?

Nationally, OSHA sets no licence, but NFPA 10 expects trained, qualified service people. Texas requires a licensee working for a company registered with the State Fire Marshal's Office, and Florida requires a licensed fire equipment dealer and a permitted technician.

What does the extinguisher tag show?

The month and year of the last service, the company and technician, and in Texas the extinguisher's type, size and location. The punched month is when it was serviced, so the next yearly visit falls due in that month a year on.

Can I do the monthly check myself?

Yes. The monthly check is yours: confirm each unit is in place, the gauge is in the green, the pin and tamper seal are intact and there is no damage, then initial the tag or a log.

Sources