Kitchen fire suppression inspection

The wet chemical system over your cooking line is serviced every six months. The technician tests the detection and release parts, replaces the fusible links, checks the gas shutoff and alarm connection, and tags the system.

Each month, check the system is armed: the pull-station pin and tamper seal are in place, the gauge reads normal and the nozzle caps are on. Wet chemical cylinders also get a hydrostatic test every twelve years.

Rules last checked Oct 23, 2026. Sources are at the foot of the page.

What the code asks for

Applies when
Wet chemical or dry chemical fire suppression system protecting commercial cooking equipment.
What the pro does
The technician tests the detection and release parts, replaces metal-alloy fusible links, checks the gas shutoff and alarm link, and tags the system.
Who may do it
Per state law. Texas and Florida license kitchen system technicians (see state entries). Manufacturer training is also normally required.
Also on its own cycle
  • Wet chemical cylinder hydrostatic test: every 12 years. NFPA 17A section 7.5.1 as quoted by the Minnesota Department of Health, 2009 edition.
Your own checks
Monthly check that the system is armed (pull-station pin and tamper seal in place, gauge normal, nozzle caps on).
Tag on the equipment
The technician attaches a dated service tag and gives the owner a report. Some cities require the contractor to upload reports.
Source: National code baseline

NFPA sells its codes rather than publishing them, so these are fire and health authorities quoting the code. They are national code, not rules for that city or state.

What it costs to miss

  • In Texas a red-tagged kitchen system means immediate notice to you and notice to the fire marshal within 24 hours.
  • In Florida, a system found in violation means a copy of the report goes to the local fire authority within 30 days.

Where the local rule differs

The state and city rules we have on file for kitchen fire suppression inspection, and how the paperwork gets filed in each.

WhereHow oftenWho may do itFiling
FloridaEvery 6 monthsFor pre-engineered systems (most restaurant hood systems), a Class D fire equipment dealer licence plus a permitted technician. Systems that are not pre-engineered need a fire protection system contractor.The tag must be attached and show the month of work. The owner gets a copy of the report at the time of inspection. If the system is in violation, a copy goes to the local fire authority within 30 days of service.
TexasEvery 6 monthsA Type K (kitchen cooking systems) or Type A (fixed system) licensee, working for a company with an Extinguisher Certificate of Registration, from the State Fire Marshal's Office.The licensee attaches a signed service tag after every service. A red tag requires owner notice at once and fire marshal notice within 24 hours.

When is yours due?

Pick your state, add the month from your tag, and see the next date and the rule behind it. Then book a licensed pro if you want one.

Optional. Used to find pros nearby.

What's on site?
  • The month punched on the tag is enough.

Free. No account needed.

Questions about kitchen fire suppression inspection

How often does an Ansul system need to be inspected?

Every six months by a licensed technician, with a monthly check by you that the system is armed.

Is this the same as hood cleaning?

No. Suppression service tests the fire system over the cooking line. Hood cleaning removes grease from the hood, ducts and fan. Most kitchens need both, on their own schedules.

Who can service a kitchen suppression system in Texas?

A Type K or Type A licensee working for a company with an Extinguisher Certificate of Registration from the State Fire Marshal's Office.

Sources

PremiseBay shows the rules and their sources. Your fire marshal, water utility or insurer has the final word for your building. How we check rules.